Type AAR/5

Type protected against HEAVY harmonics by REINFORCED capacitors and anti-harmonic blocking reactor.

  • Build-up according to CEI EN 60439 –1 & 2.
  • Capacitors according to standards EN IEC 60 831 1 & 2.
  • Cabinet IP 40 with a forced ventilation.
  • Open door IP 20 with a protective screen in poly-carbonate.

The option exists to build in a MAIN SWITCH as well as a MAIN PROTECTION !

Each step has :

  • Three-pole contactors(1) + HRC fuses
  • Appropriate for high switching frequency
  • Capacitors with high isolation voltage 600 V
  • Anti harmonic blocking reactor tuned to 14 % (135 Hz) T 40/B.

(1) Specific scale for capacitive overload !

The regulator is a microprocessor with digital readout.
The operating voltage is 230 V via a built-in transformer 400/230 V.
This gamme begins with value 22,5 kVar and and ends with 1440 kVar.

Type AAR/4

Type protected against HEAVY harmonics by REINFORCED capacitors and anti harmonic blocking reactors.

  • Build-up according to CEI EN 60439 –1 & 2.
  • Capacitors according to standards EN IEC 60 831 1 & 2.
  • Cabinet IP 40 with a forced ventilation
  • Open door IP 20 with a protective screen in poly carbonate

The option exists to build in a MAIN SWITCH as well as a MAIN PROTECTION !

Each step has :

  • Three-pole contactors(1) + HRC fuses
  • Specific scale of capacitors for capacitive overload (1)
  • Appropriate for high switching frequency
  • Capacitors with high isolation voltage 500 V
  • Anti harmonic blocking reactor tuned to 7 % (180Hz) T 40/B.

The regulator is a microprocessor with digital readout.
The operating voltage is 230 V via a built-in transformer 400/230 V.
This gamme begins with value 22,5 kVar and and ends with1440 kVar.

(1) Appropriate for a very high switching frequency

Type B50

Type protected against MEDIUM harmonics by REINFORCED capacitors.

  • Build-up according to CEI EN 60439 –1 & 2.
  • Capacitors according to standards EN IEC 60 831 1 & 2.
  • Cabinet IP 31 and/or IP 40 with or without a forced ventilation
  • Open door IP 20 with a protective screen in poly-carbonate

The option exists to build in a MAIN SWITCH as well as a MAIN PROTECTION !

Each step has :

  • Three-pole contactors (1) + HRC fuses
  • Appropriate for high switching frequency
  • Capacitors with high isolation voltage 550 V

The regulator is a microprocessor with digital readout.
The operating voltage is 230 V via a built-in transformer400/230 V.
This gamme begins with value 22,5 kVar and and ends with 1500 kVar.

(1) Specific scale for capacitive overload

 

Type B35

Type protected against MEDIUM harmonics by REINFORCED capacitors.

  • Build-up according to CEI EN 60439 –1 & 2.
  • Capacitors according to standards EN IEC 60 831 1 & 2.
  • Cabinet IP 31 and/or IP 40 with or without forced ventilation.
  • Open door IP 20 with a protective screen in poly-carbonate

The option exists to build in a MAIN SWITCH as well as a MAIN PROTECTION !

Each step has :

  • Three-pole contactors(1) + HRC fuses
  • Appropriate for high switching frequency
  • Capacitors with high isolation voltage 500 V

The regulator is a microprocessor with digital readout.
The operating voltage is 230 V via a built-in transformer400/230 V.
This gamme begins with value 17,5 kVar and and ends with 1500 kVar.

​​​​​​​ (1) Specific scale for capacitive overload

Type 230 VOLT

Type protected against MEDIUM harmonics by REINFORCED capacitors.

  • Build-up according to CEI EN 60439 –1 & 2.
  • Capacitors according to standards EN IEC 60 831 1 & 2.
  • Cabinet IP 31 and/or 40 with or without forced ventilation.
  • Open door IP 20 with a protective screen in poly-carbonate

The option exists to build in a MAIN SWITCH as well as a MAIN PROTECTION !

Each step has :

  • Three-pole contactors(1) + HRC fuses
  • Appropriate for high switching frequency
  • Capacitors with high isolation voltage 405 V

The regulator is a microprocessor with digital readout.

This scale is made on demand. 230 V is a main voltage that is only occasionally used.

​​​​​​​(1) Specific scale for capacitive overload

Capacitor banks on medium voltage

We have a large, high quality scale of FIXED and AUTOMATIC capacitor banks on medium voltage.

Possible variables :

  • Cabinet IP 40/55
  • Protection via fuses
  • Contactor
  • Current limitation reactor
  • Anti-harmonic blocking reactor
  • Current watch

Voltages that are often demanded :

  • 6,6 KVolt
  • 12 KVolt
  • 20 KVolt

 

POWER FACTOR CORRECTION UNITS – HARMONIC FILTERS – ELECTRICAL NETWORK ANALYSIS