AAR 

AAR/5

 

Appropriate for a heavy polluted network - THD (I) ≥ 60 %

 

The cabinet is constructed in robust sheet steel IP40, with a forced ventilation. Other IP values (eg IP55) are available.

Standard colour is RAL 7035.

Open door IP20 with a protective screen in poly carbonate.

She is built up modular and extensible.

 

Each step has the following characteristics :

 

  • Each bank is controlled by its own three-pole contactor (specific scale for capacitors).
  • Every bank is protected by a set of three HRC fuses.
  • The isolation voltage is 550 V.
  • Anti harmonic induction coil tuned to 14 % ( 135 Hz) T 40/B.
  • Set of bars with a large short-circuit power.
  • The regulator is a microprocessor with a digital readout
  • The operating voltage is 400 / 230 V via a built-in transformer

 

Executed in 3 types of cabinets :

  

G4M Kit :  800 x 600 x 1200 mm
G7M Kit :  800 x 600 x 2100 mm
G8M Kit : 1000 x 800 x 2100 mm